AHU 300 Ceiling
Ventilation unit

AHU 300 Ceiling

AHU series Current series

AHU 300 Himling is a ventilation unit in Ensy’s AHU series. AHU 300 Himling right and left variants have a capacity of approx. 300 m³/h and are well suited for apartments/small houses and single-family homes. The models are based on the best available technology which here has resulted in: Energy efficiency and low noise level. Very user-friendly control as well as an appealing design. AHU-300 Himling is built for ceiling mounting, alternatively wall mounting. The AHU units are of course developed to meet the requirements in today’s regulations. In addition, the units meet the requirements in the Passive House standard. Control panel with 10 meter cable is supplied loose together with the AHU unit.

TECHNICAL DATA AHU-300 Himling

  Varmebatteri -fase/spenning (50Hz/VAC) ~1 / 230
-effekt forbruk (W) 800
  Vifter -fase/spenning (50Hz/VAC) ~1 / 230
-Totalt strømtrekk begge vifter ved NORM drift (A) 0,18
-turtall ved MAX drift o/min 2100
  Sikringsstørrelse (A) 10
  Automatikksystem Integrert
  Filterklasse Superpleat F7
  Termisk isolasjon (mm) 40
  Vekt (kg) 49,5

Basic unit

Trade name

Ensy

Product name

AHU-300 HH AHU-300 HV

ErP compliance

2018

Unit category

RVU

Unit type

BVU

Drive

Variable speed

Heat recovery type

Regenerative

Thermal efficiency of HRS

90

%

qVd max

240

m³/h

PtU

100

Pa

P el,max

243

W

Sound power level   Lwa

43

dB(A)

qv ref

168

m³/h

PtU ref

50

Pa

Max external and Internal Leakage. Overpressure 250 Pa

3.9

%

Max external and Internal Leakage. Underpressure 250 Pa

4.0

%

Annual operation hours   ta

8760

 h/a

Primary energy factor    pef

2,5

Net ventilation rate    qnet

1,3

m³/hm²

MISC (ducted)

1,1

CTRL (local demand)

0,65

X value.  Motor drive characteristic  (Variable speed)

2

SPI Specific power input  (measurement)

0,00046

kW/m³/h

Total hours heating season   th  Average

5112

h/a

Total hours heating season   th  Cold

6552

h/a

Total hours heating season   th  Warm

4392

h/a

Average temperature difference  ∆Th  Average

9,5

K

Average temperature difference  ∆Th  Cold

14,5

K

Average temperature difference  ∆Th  Warm

5

K

Thermal efficiency  ηh

0,75

Specific heat capacity   Cair

0,000344

kWh/m³K

Reference natural ventilation rate qref

2,2

m³/hm³

Thermal efficiency of HRS   ηt

0,90

Defrosting period   t defr  Average

168

h/a

Defrosting period   t defr  Cold

1003

h/a

Defrosting period   t defr  Warm

0

h/a

Average temperature difference defrost  ∆Tdefr  Average

2,4

K

Average temperature difference defrost  ∆Tdefr  Cold

5,2

K

Average temperature difference defrost  ∆Tdefr  Warm

0

K

AEC average. Annual electrical consumption per 100 m²

244

kWh/a

AEC cold

244

kWh/a

AEC warm

244

kWh/a

AHS Average. Annual heating saved per m²

46,9

kWh/a

AHS Cold

91,8

kWh/a

AHS Warm

21,2

kWh/a

SEC Average. Specific energy consumption

-40,8

kWh/m²a

SEC Cold

-85,7

kWh/m²a

SEC Warm

-15,1

kWh/m²a

Efficiency Class

A

 

Airflow (Supply) [m³/h]
Pressure (Supply) [PA]
AHU-300 HH

AHU-300 HV
AHU 300 CeilingAHU 300 Ceiling
Airflow (Extract) [m³/h]
Pressure (Extract) [PA]
AHU-300 HH

AHU-300 HV
AHU 300 CeilingAHU 300 Ceiling

Dokumentnavn  

Modell

Språk

   Koblingsskjema/Wiring diagram AHU-300 H Høgre/Venstre Norsk/English
   Bruks- og Monteringsanvisning AHU-300 H Høgre/Venstre Norsk